Plan Review Notes
Plan Review Notes For Permit 00091180
Permit Number 00091180
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE ELECTRICAL RISER
 DIAGRAM,,, ONLY 1-SET OF 3/0 CONDUCTORS
 SHOWN. PLEASE SEE AMPACITIES OF 310-15
 AND 310-16 75 DEGREE COLUMN. TOTAL LOAD
 SHOWN AT 311AMPS?? PLEASE ADJUST
 CONDUCTORS.
  
 2)NOTE: ALSO, PLEASE SEE THE FOLLOWING
 ARTS:373-7/373-8/380-3 FOR EQUIPMENT ETC
 BEING USED AS RACEWAYS TO OTHER DISC`S
 PANELS ETC. IF THE MAIN DISC IS BEING
 USED AS RACEWAY? THEN IT MUST MEET ALL
 CODES REFERENCED IN NEC. ALSO PLEASE
 PLACE NOTE ON PLAN FOR THOSE REQ`MENTS
 TO BE MET.IF NOT SHOW SECOND CONDUIT
 FROM METERCAN TO 2ND MAIN DISC.
  
 3)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52 AND PLEASE SHOW PANEL "C" ON
 ELECTRICAL PLANS PER 215-5. NOTE 110-26
 FOR CLEARENCES ABOUT POOL EQUIPMENT.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372