Plan Review Notes For Permit 00091137 |
Permit Number |
00091137 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | 1)NOTE: PLEASE NOTE THAT THERE IS STILL | | NO ELECTRICAL SHOWN?? APPLICATION AND | | EXPLANATION OF WORK MENTIONS NEW 4TON | | A/C. WHAT SIZE WAS EXISTING? SHOWN | | LOAD CALCS IF INCREASING LOAD. | | | | 2)NOTE: PLEASE PROVIDE FLOOR LAYOUT FOR | | ALL OTHER ELECTRICAL WORK BEING DOWN. | | SHOW LOCATIONS OF WORK. | | | | PLEASE SUBMIT THE ABOVE INFORMATION AND | | SHOW WORK TO BE DONE. IF THERE ARE ANY | | QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096-EXT8372 | | | | ELECTRIC UNDER SEPARATE PERMIT | | BUILDING PERMIT ISSUED SEPARATE |
|