Plan Review Notes
Plan Review Notes For Permit 00090804
Permit Number 00090804
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISOS
  
 PLEASE REVISED PLANS SHOWING CORRECT
 LOCATION OF 6" FIRE SPRINKLER LINE IN
 RELATION TO THE PROPOSED INLET.
  
 NEW FIRE HYDRANT LOCATION SHOULD BE 2'
 MIN INSIDE OF CURB.
  
 PROVIDE DRAINAGE FLOW ARROWS AS SHOWN.
  
 A MINIMUM OF TWO SETS OF PLANS MUST
 SUBMITTED FOR APPROVAL AND UTILITY
 INSPECTOR.
 ATTENTION MANNY GONZALEZ
 ENGINEERING SERVICES
 1000 45TH ST SUITE 15
 WEST PALM BEACH, FL 33407
 561 659 8040 EXT .2306
  
 ALSO A MINIMUM OF 2 SHOP DRAWINGS
 SUBMITTALS MUST ALSO BE SUBMITTED.
  
 SHOW EXISTING FIRE HYDRANT (TO REMAIN)
  
 YOU MAY SAVE A VALVE SINCE THE TAP
 REQUIRES A TAP AND FIRE HYDRANT IS NOT
 FAR FROM TAP LOCATION.
  
 NEW PIPE SHALL BE CLASS52, CEMENT LINE
 D, DIP (FIRE HYDRANT LINE)