Plan Review Notes For Permit 00090804 |
Permit Number |
00090804 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISOS | | | | PLEASE REVISED PLANS SHOWING CORRECT | | LOCATION OF 6" FIRE SPRINKLER LINE IN | | RELATION TO THE PROPOSED INLET. | | | | NEW FIRE HYDRANT LOCATION SHOULD BE 2' | | MIN INSIDE OF CURB. | | | | PROVIDE DRAINAGE FLOW ARROWS AS SHOWN. | | | | A MINIMUM OF TWO SETS OF PLANS MUST | | SUBMITTED FOR APPROVAL AND UTILITY | | INSPECTOR. | | ATTENTION MANNY GONZALEZ | | ENGINEERING SERVICES | | 1000 45TH ST SUITE 15 | | WEST PALM BEACH, FL 33407 | | 561 659 8040 EXT .2306 | | | | ALSO A MINIMUM OF 2 SHOP DRAWINGS | | SUBMITTALS MUST ALSO BE SUBMITTED. | | | | SHOW EXISTING FIRE HYDRANT (TO REMAIN) | | | | YOU MAY SAVE A VALVE SINCE THE TAP | | REQUIRES A TAP AND FIRE HYDRANT IS NOT | | FAR FROM TAP LOCATION. | | | | NEW PIPE SHALL BE CLASS52, CEMENT LINE | | D, DIP (FIRE HYDRANT LINE) |
|