Plan Review Notes For Permit 00090754 |
Permit Number |
00090754 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) THE MECHANICAL ROOM AND STORAGE ROOM | | ARE TO BE ONE HOUR FIRE SEPARATED IF | | TENANT SPACE IS NOT FIRE SPRINKLER | | PROTECTED. DOORS TO THESE ROOMS ARE TO | | BE 45 MINUTE FIRE RATED WITH CLOSING | | DEVICES IF NO FIRE SPRINKLERS ARE | | PRESENT AND THE ROOMS HAVE TO BE ONE | | HOUR RATED. | | 2) INTERIOR FINISH IN OFFICES TO BE | | CLASS A, B OR C.INTERIOR FINISH IN | | EXITS TO BE CLASS A OR B. |
|