2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 OF EXISTING HOUSE. CALCULATIONS ARE TO
 INCLUDE ALL NEW LOADS, HEAT PUMP, MOTOR/
 S/, LIGHTS ETC,
  
 2)NOTE:PLEASE INCLUDE HEATER ON PLANS
 THAT SHOW THE ELECTRICAL DIAGRAM.
  
 3)NOTE: PLEASE NOTE THAT THIS WILL BE
 REQ`D ON ALL SUBMITTALS WITH HEAT PUMPS.
 215-5
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  