2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | OF EXISTING HOUSE. CALCULATIONS ARE TO | | INCLUDE ALL NEW LOADS, HEAT PUMP, MOTOR/ | | S/, LIGHTS ETC, | | | | 2)NOTE:PLEASE INCLUDE HEATER ON PLANS | | THAT SHOW THE ELECTRICAL DIAGRAM. | | | | 3)NOTE: PLEASE NOTE THAT THIS WILL BE | | REQ`D ON ALL SUBMITTALS WITH HEAT PUMPS. | | 215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 561-659-8096 EXT 8372 |
|