Notes
Date Text
2001-03-14 00:00:00DENIED;
  
 1.FLOORSHALL BE USED INPLACE OF A HUB
 DRAIN. FLOOR DRAIN SHALL BE PRIMED.
  
 2.SHEET A-1 WATER HEATER IS IN A DIRRENT
 LOCATION THAN P-3.1 AND NOT SHOWD AT
 ALL ON P-2.1.
  
 3.P-5 FLOOR DRAIN IN BATHROOM IS MISSING
 FROM SANITARY RISER DIAGRAM.
  
 4.WHY IS A MECHANICAL VENT NEEDED? TEN
 FEET OF PIPE ABOVE THE CEILING AND THE
 PLUMBER COULD TIE INTO THE VENT SYSTEM
  
  