Plan Review Notes
Plan Review Notes For Permit 00090413
Permit Number 00090413
Review Stop E
Sequence Number 2
Notes
Date Text
2001-03-07 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SHOW COMPLETED LOAD
 CALCULATIONS. ALL CONTINUOUS LOADS ARE
 TO BE SHOWN AT 125% PER 215-2&3 AND
 210-20
  
 2)NOTE: PLEASE PROVIDE KVA RATING OF
 TRANSFORMER. PLEASE PROVIDE
 CLARIFICATION ON INSTALLATION AT
 CEILING AS TO MEET 450-13
  
 3)NOTE: PLEASE PROVIDE NOTE ON PLAN
 UNDER LIGHTING FIXTURE SCHEDULE.
 " ALL FIXTURES AND FIXTURE COMPONETS
 ARE TO BE UL LISTED"
  
 PLEASE PROVIDE THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372