Plan Review Notes For Permit 00090413 |
Permit Number |
00090413 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-03-07 00:00:00 | **************** UNSAT *************** | | | | 1)NOTE: PLEASE SHOW COMPLETED LOAD | | CALCULATIONS. ALL CONTINUOUS LOADS ARE | | TO BE SHOWN AT 125% PER 215-2&3 AND | | 210-20 | | | | 2)NOTE: PLEASE PROVIDE KVA RATING OF | | TRANSFORMER. PLEASE PROVIDE | | CLARIFICATION ON INSTALLATION AT | | CEILING AS TO MEET 450-13 | | | | 3)NOTE: PLEASE PROVIDE NOTE ON PLAN | | UNDER LIGHTING FIXTURE SCHEDULE. | | " ALL FIXTURES AND FIXTURE COMPONETS | | ARE TO BE UL LISTED" | | | | PLEASE PROVIDE THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|