Plan Review Notes
Plan Review Notes For Permit 00090261
Permit Number 00090261
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE ART:S 230-76 AND 230-
 -79 FOR THE REQ`DDISCONNECTING MEANS
 SHUNT TRIP IS NOT A SERVICE RATED DISC.
  
 2)NOTE: PLEASE SEE 230-72 FOR GROUPING
 OF SERVICE DISCONNECTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372