Plan Review Notes For Permit 00090249 |
Permit Number |
00090249 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) GARAGE DOORS WHEN OPENED ARE NOT TO | | INTERFERE WITH FIRE SPRINKLER OPERATION | | IN THE GARAGES. | | 2) FIRE SPRINKLER CANNOT BE OMITTED FROM | | ENTRY FOYER IF THAT IS THE ONLY MEANS OF | | EGRESS. | | 3) SOFFITS ARE NOT TO INTERFERE WITH | | FIRE SPRINKLER HEAD DISCHARGE. | | 4) TOWNHOUSE UNITS ARE TO BE SEPARATED | | FROM ONE ANOTHER BY AT LEAST TWO HOUR | | FIRE WALLS. | | APPROVED PROVISO: |
|