2001-01-08 00:00:00 | CHECKLIST: |
| 1-ENERGY CALCULATIONS: |
| -REVISE NUMBER OF UNITS. SEE PLANS. |
| -REVISE NUMBER OF BEDROOMS. (THREE) |
| -REVISE OWNER INFORMATION AND FILL IN |
| ALL INFORMATION ON TOP OF FORM. |
| -OWNER/AGENT TO DATE FORM. |
| 2-WALK-IN CLOSETS AT ALL UNITS DON'T |
| COMPLY WITH THE FAIR HOUSING ACT. |
| SEE PAGE 3.15 FOR MINIMUM WIDTH FOR A |
| WALK-IN CLOSET. DELETING THE SHELF AND |
| ROD ON EITHER SIDE WILL COMPLY WITH |
| THE FAIR HOUSING ACT. |
| -SHELF ON ONE SIDE WILL BE ACCEPTABLE |
| WHEN THERE IS CLEAR MINIMUM WIDTH OF |
| 5'-0" WITHOUT INCLUDING THE SHELF. |
| 3-PROVIDE SOIL TEST REPORT AS PER SECT'N |
| 1804.2.7.2 AND TABLE 1804.2.7.3 OF |
| CITY AMENDMENTS TO SBC 1997. |
| 4-SPECIFY HARDWARE FOR ENTRY ACCESSIBLE |
| DOORS FOR COMPLIANCE WITH THE FAIR |
| HOUSING ACT. |
| 5-REVISE DIMENSIONS ON OPTION #5 PAGE 2 |
| TO MATCH FLOOR PLAN. |
| 6-STORM PANELS: |
| -PROVIDE COMPLETE INFORMATION, INCLUD'G |
| COMPLETE INSTALLATION SCHEDULE AS PER |
| CITY SAMPLE ATTACHED AND KEY PLAN. |
| ALSO, CLEARLY HIGHLIGHT DRAWINGS |
| INDICATING MOUNTING CONDITIONS AND |
| ANCHOR TO BE USED ACCORDING TO DESIGN |
| PRESSURES, STRUCTURE TO BE ATTACHED |
| (THIS IS CONCRETE BLOCK CONSTRUCTION, |
| NOT 3000PSI CONCRETE), EDGE DISTANCE, |
| PANEL SPAN AND CONNECTION TYPE. |
| NOTE: IF COMPLETE INFORMATION IS NOT |
| SUBMITTED AT TIME OF RESUBMITTAL, THEN |
| A SEPARATE PERMIT WILL BE REQUIRED. |
| 7-PROVIDE CALCULATIONS FOR CROSS VENTI- |
| LATION AT EACH UNIT ATTIC SPACE. |
| SECTION 2309.7 SBC 1997. |
| 8-PROVIDE PRODUCT APPROVAL FOR: |
| -INSWING ENTRY DOOR. |
| -INSWING FRENCH DOOR WITH SIDELITES. |
| -BBQ UL LISTING. |
| -CERTIFICATION FROM MANUFACTURER'S |
| ENGINEER STATING THAT CONCRETE BLOCK |
| EQUIVALENT THICKNESS WILL PROVIDE TWO |
| HOUR FIRE RATING ACCORDING TO ASTM |
| C140. SECTION 709.3 SBC 1997. |
| -OUTSWING FRENCH DOORS. |
| 9-PROVIDE STRUCTURAL BUCK DETAIL FOR |
| SLIDING GLASS DOORS. SEC 104.2 CITY |
| AMENDMENTS. |
| 10-PROVIDE COMPLETE DETAIL/SPECIFICATION |
| FOR CEILING CONSTRUCTION AT FRONT AND |
| BACK PORCH. SEC 2504 SBC 1997. |
| NOTE: INCLUDE FASTENER TYPE & SPACING. |
| 11-PROVIDE PRODUCT APPROVAL FOR GARAGE |
| DOORS. |
| 12-CONTRACTOR TO UPDATE INSURANCE AND |
| WORKERS COMPENSATION. |