Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) ON SEPTEMBER 6, 2000, THIS WRITER | | CONTACTED MR. NORDINE BY TELEPHONE. MR. | | NORDINE ADVISED THAT 8 TO 9 DOORS | | THROUGHOUT THE BUILDING WILL BE REPLACED | | TO 1 1/2 RATED FIRE DOORS. ALSO MR. | | NORDINE ADVISED THAT 5/8 TYPE X SHEET | | ROCK WILL BE USED. | | 2) FIRE DOORS TO BE USED ARE TO BE | | PROPERLY LABELED IN ACCORDANCE WITH | | NFPA 80, FIRE DOORS AND WINDOWS, SECTION | | 1-6.1. FIRE DOORS THAT ARE INSTALLED TO | | EQUIPPED WITH SELF-CLOSING DEVICES PER | | NFPA 80, FIRE DOORS AND WINDOW, SECTION | | 2-4.1.2. METAL DOOR FRAMES ARE TO | | BE LABELED PER NFPA 80, FIRE DOORS AND | | WINDOWS, SECTION 2-3.1.1 | | APPROVED PROVISO: |
|