2001-11-13 00:00:00 | ******************* UNSAT ************ |
| |
| 1)NOTE: PLEASE NOTE THAT THE PLANS |
| SUBMITTED FOR GUEST/GARAGE DO NOT |
| CORRELATE WITH PLANS FORMAIN HOUSE |
| SERVICE. TWO PLANS /TWO SERVICES? |
| |
| 2)NOTE: PLEASE CLARFIY SIZE OF METERCAN, |
| SHOWN AS EXISTING? LOAD SHOWN AT 269.9A |
| |
| 3)NOTE: PLEASE NOTE THAT ON GUEST HOUSE |
| METER AND TWO DISCONNECTS ARE SHOWN, BUT |
| DOES NOT SHOW WHERE PANEL IS ON PLANS? |
| NOTE NEXT TO SERVICE SAYS, "GUEST HOUSE |
| PANEL" , THEN WHERE IS MAIN DISCONNECT |
| SHOWN ON RISER DIAGRAM? |
| |
| 4)NOTE: PLEASE NOTE MISSING GROUNDING |
| AT DETACHED MAIN HOUSE. 250-32. |
| |
| 5)NOTE: PLEASE INDICATE MCB FOR PANEL |
| AT MAIN HOUSE DETACHED FROM GUEST HOUSE |
| SERVICE. 225-31 |
| |
| 6)NOTE: PLEASE NOTE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS BETWEEN MAIN DISC`S |
| AND PANELS. 250-122 |
| |
| 7)NOTE: PLEASE CLARIFY 2/0`S SHOWN FOR |
| 100A EQUIPMENT? |
| |
| 8) NOTE: PLEASE LIST THE REQ`D BATH(S) |
| CIRCUIT(S) PER 210-11-C-3. |
| MUST BE 20A AND #12AWG. |
| ARE THE GFI CIRCUITS THAT ARE SHOWN ON |
| PANEL SCHEDULE FOR THIS? |
| |
| 9)NOTE: PLEASE SHOW GARAGE ON THE |
| ELECTRICAL PLAN AND SHOW REQ`D ELEC. |
| FOR GARAGE. PLAN SHOW GARAGE AS DETACHED |
| ?? PLEASE CLARIFY. |
| |
| PLEASE MAKE THE ABOVE CORRECTIONS AND |
| SUBMIT THE INFORMATION FOR REVIEW. IF |
| THERE ARE ANY QUESTIONS, PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-659-8096 EXT 8372 |