Plan Review Notes
Plan Review Notes For Permit 00090107
Permit Number 00090107
Review Stop E
Sequence Number 3
Notes
Date Text
2001-11-13 00:00:00******************* UNSAT ************
  
 1)NOTE: PLEASE NOTE THAT THE PLANS
 SUBMITTED FOR GUEST/GARAGE DO NOT
 CORRELATE WITH PLANS FORMAIN HOUSE
 SERVICE. TWO PLANS /TWO SERVICES?
  
 2)NOTE: PLEASE CLARFIY SIZE OF METERCAN,
 SHOWN AS EXISTING? LOAD SHOWN AT 269.9A
  
 3)NOTE: PLEASE NOTE THAT ON GUEST HOUSE
 METER AND TWO DISCONNECTS ARE SHOWN, BUT
 DOES NOT SHOW WHERE PANEL IS ON PLANS?
 NOTE NEXT TO SERVICE SAYS, "GUEST HOUSE
 PANEL" , THEN WHERE IS MAIN DISCONNECT
 SHOWN ON RISER DIAGRAM?
  
 4)NOTE: PLEASE NOTE MISSING GROUNDING
 AT DETACHED MAIN HOUSE. 250-32.
  
 5)NOTE: PLEASE INDICATE MCB FOR PANEL
 AT MAIN HOUSE DETACHED FROM GUEST HOUSE
 SERVICE. 225-31
  
 6)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTORS BETWEEN MAIN DISC`S
 AND PANELS. 250-122
  
 7)NOTE: PLEASE CLARIFY 2/0`S SHOWN FOR
 100A EQUIPMENT?
  
 8) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 ARE THE GFI CIRCUITS THAT ARE SHOWN ON
 PANEL SCHEDULE FOR THIS?
  
 9)NOTE: PLEASE SHOW GARAGE ON THE
 ELECTRICAL PLAN AND SHOW REQ`D ELEC.
 FOR GARAGE. PLAN SHOW GARAGE AS DETACHED
 ?? PLEASE CLARIFY.
  
 PLEASE MAKE THE ABOVE CORRECTIONS AND
 SUBMIT THE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372