2001-11-16 00:00:00REVISION DENIED
  
 1) PROVIDE AN EMERGENCY ESCAPE AND
 RESCUE OPENING FOR THE SECOND FLOOR
 GUEST ROOM PER 97 SBC SEC. 1005.4.1.
 THE WINDOW MUST HAVE A MINIMUM NET CLEAR
 OPENING OF 5.7 SQ.FT. WITH A MINIMUM NET
 CLEAR OPENING HEIGHT OF 24" AND MINIMUM
 NET CLEAR OPENING WIDTH OF 20". THE SILL
 HEIGHT CAN NOT BE MORE THAN 44" PER 97
 SBC SEC.1005.4.4 AND 1005.4.3.
  
 2)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - STRUCTURAL WINDOW MULLIONS
 - STORM PANELS OR IMPACT GLASS
  
 3) PROVIDE ACCESS TO ATTIC SPACE PER
 97 SBC SEC. 2309.6.
  
 4) EXTERIOR EXITWAY STAIRS:
 EXTERIOR STAIRS SHALL BE SEPARATED FROM
 THE INTERIOR OF THE BUILDING BY WALLS
 WITH A FIRE RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR, WITH FIXED OR SELF-
 CLOSING OPENING PROTECTIVES AS REQUIRED
 FOR ENCLOSED STAIRS. PROTECTION SHALL
 EXTEND VERTICALLY FROM THE GROUND TO A
 POINT 10 FEET ABOVE THE TOPMOST LANDING
 OR THE ROOF LINE WHICHEVER IS LOWER AND
 HORIZONTALLY 10 FEET FROM EACH SIDE OF
 THE STAIRWAY. OPENINGS WITHIN THE 10
 FOOT HORIZONTAL EXTENSION OF THE
 PROTECTED WALLS BEYOND THE STAIRWAY
 SHALL BE EQUIPPED WITH FIXED 3/4- HOUR
 ASSEMBLIES. 97 SBC SEC. 1006.2.4 THE NEW
 DOORS AND WINDOWS IN THIS AREA MUST
 COMPLY. SEE 97 SBC SEC. 705.1.3 FOR
 APPROVED TYPES OF FIRE WINDOWS AND DOORS
  
  