2001-11-16 00:00:00 | REVISION DENIED |
| |
| 1) PROVIDE AN EMERGENCY ESCAPE AND |
| RESCUE OPENING FOR THE SECOND FLOOR |
| GUEST ROOM PER 97 SBC SEC. 1005.4.1. |
| THE WINDOW MUST HAVE A MINIMUM NET CLEAR |
| OPENING OF 5.7 SQ.FT. WITH A MINIMUM NET |
| CLEAR OPENING HEIGHT OF 24" AND MINIMUM |
| NET CLEAR OPENING WIDTH OF 20". THE SILL |
| HEIGHT CAN NOT BE MORE THAN 44" PER 97 |
| SBC SEC.1005.4.4 AND 1005.4.3. |
| |
| 2)PROVIDE (2) CURRENT AND COMPLETE |
| COPIES OF SBCCI OR METRO-DADE PRODUCT |
| APPROVALS FOR: |
| - STRUCTURAL WINDOW MULLIONS |
| - STORM PANELS OR IMPACT GLASS |
| |
| 3) PROVIDE ACCESS TO ATTIC SPACE PER |
| 97 SBC SEC. 2309.6. |
| |
| 4) EXTERIOR EXITWAY STAIRS: |
| EXTERIOR STAIRS SHALL BE SEPARATED FROM |
| THE INTERIOR OF THE BUILDING BY WALLS |
| WITH A FIRE RESISTANCE RATING OF NOT |
| LESS THAN 1 HOUR, WITH FIXED OR SELF- |
| CLOSING OPENING PROTECTIVES AS REQUIRED |
| FOR ENCLOSED STAIRS. PROTECTION SHALL |
| EXTEND VERTICALLY FROM THE GROUND TO A |
| POINT 10 FEET ABOVE THE TOPMOST LANDING |
| OR THE ROOF LINE WHICHEVER IS LOWER AND |
| HORIZONTALLY 10 FEET FROM EACH SIDE OF |
| THE STAIRWAY. OPENINGS WITHIN THE 10 |
| FOOT HORIZONTAL EXTENSION OF THE |
| PROTECTED WALLS BEYOND THE STAIRWAY |
| SHALL BE EQUIPPED WITH FIXED 3/4- HOUR |
| ASSEMBLIES. 97 SBC SEC. 1006.2.4 THE NEW |
| DOORS AND WINDOWS IN THIS AREA MUST |
| COMPLY. SEE 97 SBC SEC. 705.1.3 FOR |
| APPROVED TYPES OF FIRE WINDOWS AND DOORS |
| |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)659-8096 EXT.8202 |