2001-01-08 00:00:00 | **************** UNSAT **************** |
| |
| 1)NOTE: PLEASE CLARIFY PLANS, YOU SHOW |
| GARAGE AS FUTURE BUT ARE SHOWING AS NEW |
| ROOF ETC??? ELECTRIC REQ`D IF NEW? |
| |
| 2)NOTE: PLEASE SHOW NEW CU FOR A/C |
| DISCONNECT PER 440-11 AND WP GFI. |
| |
| 3)NOTE: PLEASE NOTE PER FIRST REVIEW, |
| MISSING GFI FOR REAR OF BLDG. 210-52E |
| |
| 4)NOTE: PLEASE SHOW WINDOW A/C BEING TAK |
| -EN OUT? IS A/C ON FIRST FLOOR FEEDING |
| SECONG FLOOR? |
| |
| 5)NOTE: LOAD CALCULATIONS (SQ FT) DOES- |
| -NOT MATCHFLOOR SQ FT.?? IS FIRST |
| FLOOR AND SECOND FLOOR ON SAME PANEL? |
| |
| 6)NOTE: SINCE FIRST REVIEW A NEW SERVICE |
| IS BEING SHOWN.. 100AMP PANEL W/ 2/0 |
| WIRE? IS THIS CORRECT? |
| PLEASE SUBMIT AIC RATING OF NEW MAIN |
| DISCONNECT AND PANEL. MUST BE RATED FOR |
| AVAILABLE FAULT CURRENT PER 110-9 AND |
| 215-5. |
| |
| 7)NOTE: PLEASE SHOW BATH(S) CIRCUIT(S) |
| REQ`D PER 210-11-C-3 AND 210-52D. #12 AN |
| 20AMP. |
| |
| 8)NOTE: PLEASE NOTE;YOU SHOW DISCONNECTS |
| ON AHU AND WATER HEATER? NOTE 110-26 FOR |
| DISC CLEARENCE. PANEL IS WITHIN SIGHT |
| ACCROSS HALL?S |
| |
| 9)NOTE: PLEASE CHECK LOAD SHOWN FOR |
| WATER HEATER ON #12 AND 20AMP BRKR? |
| PLEASE NOTE THAT OCP FOR A 4500W WATER |
| HEATER MUST BE 125%. 4500W EXCEEDS 80% |
| OF BRKR. |
| |
| 10)NOTE: PLEASE SEE 250-122 AND SIZE |
| EQUIPMENT GROUNDING CONDUCTOR FROM |
| MAIN TO PANEL. |
| |
| 1)NOTE: PLEASE SHOW EGRESS LIGHTING FOR |
| MAIN GUEST ROOM FIRST FLOOR. PER 210-70 |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |