2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE CLARIFY PLANS, YOU SHOW
 GARAGE AS FUTURE BUT ARE SHOWING AS NEW
 ROOF ETC??? ELECTRIC REQ`D IF NEW?
  
 2)NOTE: PLEASE SHOW NEW CU FOR A/C
 DISCONNECT PER 440-11 AND WP GFI.
  
 3)NOTE: PLEASE NOTE PER FIRST REVIEW,
 MISSING GFI FOR REAR OF BLDG. 210-52E
  
 4)NOTE: PLEASE SHOW WINDOW A/C BEING TAK
 -EN OUT? IS A/C ON FIRST FLOOR FEEDING
 SECONG FLOOR?
  
 5)NOTE: LOAD CALCULATIONS (SQ FT) DOES-
 -NOT MATCHFLOOR SQ FT.?? IS FIRST
 FLOOR AND SECOND FLOOR ON SAME PANEL?
  
 6)NOTE: SINCE FIRST REVIEW A NEW SERVICE
 IS BEING SHOWN.. 100AMP PANEL W/ 2/0
 WIRE? IS THIS CORRECT?
 PLEASE SUBMIT AIC RATING OF NEW MAIN
 DISCONNECT AND PANEL. MUST BE RATED FOR
 AVAILABLE FAULT CURRENT PER 110-9 AND
 215-5.
  
 7)NOTE: PLEASE SHOW BATH(S) CIRCUIT(S)
 REQ`D PER 210-11-C-3 AND 210-52D. #12 AN
 20AMP.
  
 8)NOTE: PLEASE NOTE;YOU SHOW DISCONNECTS
 ON AHU AND WATER HEATER? NOTE 110-26 FOR
 DISC CLEARENCE. PANEL IS WITHIN SIGHT
 ACCROSS HALL?S
  
 9)NOTE: PLEASE CHECK LOAD SHOWN FOR
 WATER HEATER ON #12 AND 20AMP BRKR?
 PLEASE NOTE THAT OCP FOR A 4500W WATER
 HEATER MUST BE 125%. 4500W EXCEEDS 80%
 OF BRKR.
  
 10)NOTE: PLEASE SEE 250-122 AND SIZE
 EQUIPMENT GROUNDING CONDUCTOR FROM
 MAIN TO PANEL.
  
 1)NOTE: PLEASE SHOW EGRESS LIGHTING FOR
 MAIN GUEST ROOM FIRST FLOOR. PER 210-70
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.