Plan Review Notes For Permit 00090054 |
Permit Number |
00090054 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED: | | 1. PROVIDE BETTER QUALITY DRAWING WITH | | DETAILED INFORMATION ON CFM @ DROPS | | AND ALL DUCT SIZES | | 2.DUCT R-VALUE TO BE SHOWN | | 3. CONDENSING UNITS ON ROOF TO BE MOUNT- | | ED ON STANDS WITH MINIMUM CLEARANCE OF | | 18" BETWEEN ROOF SURFACE AND BOTTOM OF | | SUPPORT STRUCTURE OF STAND AND MEETING | | WIND LOAD RATINGS. PROVIDE ENGINEERED | | INFORMATION ON STAND. | | 4. IS DUCT LOCATED IN ATTIC OR IN SOFFIT | | BELOW CEILING? P[ROVIDE INFORMATION. | | 5 PROVIDE CONDENSATE DRAINLINE LOCATION | | INFORMATION. |
|