Plan Review Notes For Permit 00081607 |
Permit Number |
00081607 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) NO CUT SHEETS PROVIDED FOR FIRE | | SPRINKLER HEADS PLANNED FOR USE. | | PLEASE PROVIDE CUT SHEETS FOR FIRE | | SPRINKLER HEADS THAT WILL BE USED | | INSIDE THE BUILDING. | | 2) ENTIRE FIRE SPRINKLER AND STANDPIPE | | SYSTEM IS SUBJECT TO FIRE RESCUE | | APPROVAL. | | 3) SOFFITS ARE NOT TO INTERFERE WITH | | ANY FIRE SPRINKLER HEAD DISCHARGE | | PATTERNS. | | 4) FIRE DEPARTMENT CONNECTION TO BE | | NO MORE THAN 150 FEET TO A FIRE | | HYDRANT. | | APPROVED PROVISO: |
|