2001-01-08 00:00:00PIPING FROM METER SHALL BE A MIN. OF
 1 1/4" PER SGC TABLE 305.4(A).
  
 MIN.SIZE LINE TO POOL HEATER SHALL BE
 1 1/4"PER TABLE 305.4(A).
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.