Plan Review Notes
Plan Review Notes For Permit 00081533
Permit Number 00081533
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) THE FIRE DEPARTMENT CONNECTION
 LOCATED ON THE NORTH SIDE OF THE
 BUILDING WILL BE BLOCKED BY A SECURITY
 FENCE LOCATED AT THE SERVICE ROAD AND
 THE EAST VEHICLE ENTRY POINT. PLEASE
 RELOCATE THIS DEVICE SO THAT IT COULD
 BE USED BY FIRE RESCUE IN AN EMERGENCY.
 2) GARAGE DOORS WHEN OPENED ARE NOT TO
 INTERFERE WITH FIRE SPRINKLER OPERATION
 IN THE GARAGES.
 3) FIRE SPRINKLERS CANNOT BE OMITTED
 FROM ENTRY FOYER IF THAT IS THE ONLY
 MEANS OF EGRESS.
 4) SOFFITS ARE NOT TO INTERFERE WITH
 FIRE SPRINKLER HEAD DISCHARGE.
 5) TOWNHOUSE UNITS ARE TO BE SEPARATED
 FROM ONE ANOTHER BY AT LEAST TWO HOUR
 FIRE WALLS.
 APPROVED PROVISO: