Plan Review Notes
Plan Review Notes For Permit 00081520
Permit Number 00081520
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00A 3/4" GALV.LINE CANNOT SUPPLY A SYSTEM
 LOAD OF 110,000 BTU'S.SEE SGC TABLE
 305.4(A).MIN.SIZE SHALL BE 1".