2001-01-08 00:00:00PROVISO;
  
 1.PAGE A-5 (HOT WATER HEATER AT WEST
 BUILDING) SHOW CALCULATIONS FOR
 COMBUSTION AIR AS REQUIRED BY STANDARD
 GAS CODE.
  
 2.SHOW TYPE LOCATION,SIZE AND TERMINA-
 TION OF GAS VENT AS REQUIRED BY SMC.
  
 3.SEPARATE PERMIT REQUIRED FOR GAS WORK.
 DRAWINGS REQUIRED WITH APPLICATION
 SHOWING LONGEST RUN AND BTU'S FOR
 EACH APPLIANCE.
  
  