2001-03-19 00:00:00****************PROVISO*****************
  
 AS PER NFPA 90A 4-4.4.3, FAN SHUTDOWN
 BY DUCT SMOKE DETECTOR SHALL HAVE
 NOTIFICATION TO HORN/STROBE ALARM IN
 NORMALLY OCCUPIED AREAS.