Plan Review Notes For Permit 00081232 |
Permit Number |
00081232 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-02-27 00:00:00 | 1) ALL WINDOWS WITHIN 10 FEET OF THE | | REQUIRED EXTERIOR EXIT STAIR FROM THE | | SECOND FLOOR MUST BE FIRE RATED. | | ACCORDING TO NFPA 80, THE STANDARD FOR | | FIRE DOORS AND WINDOWS, THE FOLLOWING | | REQUIREMENTS ARE TO BE MET FOR | | INSTALLATION. | | A) FIRE WINDOW FRAMES SHALL BE LABELED. | | B) ONLY LABELED FIRE PROTECTION RATED | | GLAZING MATERIAL SHALL BE USED IN | | WINDOWS. | | C) EACH INDIVIDUAL GLAZING UNIT SHALL | | BE IDENTIFIED WITH A LABEL. THE LABEL | | SHALL BE VISIBLE AFTER INSTALLATION. | | 2) PLEASE PROVIDE A DRAWING OF THE | | STAIRS IN RELATION TO THE WINDOWS THAT | | WILL BE FIRE RATED. ALSO PLEASE PROVIDE | | INFORMATION ON WINDOW SIZES THAT WILL | | BE PROTECTED BY FIRE RATED GLASS. | | PLEASE BE ADVISED THAT GLASS BLOCKS MAY | | BE USED BUT THAT THEY MUST BE LABELED. | | | | APPROVED PROVISO: | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|