Plan Review Notes
Plan Review Notes For Permit 00081232
Permit Number 00081232
Review Stop E
Sequence Number 3
Notes
Date Text
2001-03-01 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW
 COMING IN SHOWING NEW SERVICE?
 PLEASE NOTE THAT THE VALUE ON PERMIT
 APPLICATION FOR ELECTRICAL MUST BE
 INCREASED TO ACCOMADATE.
  
 2)NOTE: PLEASE NOTE THERE IS NOT ENOUGH
 INFORMATION FOR REVIEW OF NEW SERVICE.
 PLEASE SUBMIT A ONE LINE DIAGRAM/ ELEC
 RISER DIAGRAM. NEED ALOT MORE DETAIL ON
 EQUIPMENT. WIRE SIZES/CONDUIT SIZES
 ECT ECT.PANEL SCHEDULES?
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE NOTE LIGHT FIXTURE IN
 CLOSET
 NOT PERMITTED AS SHOWN PER 410-8.
  
 5)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT
 #`S ON PLANS THAT CORRELATE WITH PANEL
 SCHEDULS.215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW