Plan Review Notes
Plan Review Notes For Permit 00081232
Permit Number 00081232
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************DENIED**********************
 1. 1997 SMC 609.1.1 REQUIRES PUBLIC EXIT
 CORRIDORS IN HOTELS, HOSPITALS, INSTITU-
 TIONS, AND SIMILAR OCCUPANCIES SHALL NOT
 BE USED AS PLENUMS FOR ADJOINING AREAS.
 PROVIDE INFORMATION ON RETURN AIR PATH
 TO AIR HANDLING EQUIPMENT TO COMPLY WITH
 THIS REQUIREMENT.
  
 NOTE: NFPA 90A 4-4.4 REQUIRES FAN SHUT
 DOWN BY DUCT SMOKE DETECTOR TO BE TIED
 TO BUILDING FIRE ALARM SYSTEM IF ONE
 EXISTS OR TIED TO HORN AND STROBE FOR
 NOTIFICATION IF NO BUILDING FIRE ALARM
 SYSTEM EXISTS.
 ALL AIR HANDLING EQUIPMENT OVER 2000 CFM
 WILL REQUIRE FAN SHUT DOWN BY DUCT SMOKE
 DETECTOR AND 1997 SMC 406.2 REQUIRES ALL
 EQUIPMENT SERVING AREAS USED FOR EGRESS
 EVEN IF LESS THAN 2000 CFM HAVE FAN SHUT
 DOWN BY DUCT SMOKE DETECTOR.