Plan Review Notes For Permit 00081232 |
Permit Number |
00081232 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************DENIED********************** | | 1. 1997 SMC 609.1.1 REQUIRES PUBLIC EXIT | | CORRIDORS IN HOTELS, HOSPITALS, INSTITU- | | TIONS, AND SIMILAR OCCUPANCIES SHALL NOT | | BE USED AS PLENUMS FOR ADJOINING AREAS. | | PROVIDE INFORMATION ON RETURN AIR PATH | | TO AIR HANDLING EQUIPMENT TO COMPLY WITH | | THIS REQUIREMENT. | | | | NOTE: NFPA 90A 4-4.4 REQUIRES FAN SHUT | | DOWN BY DUCT SMOKE DETECTOR TO BE TIED | | TO BUILDING FIRE ALARM SYSTEM IF ONE | | EXISTS OR TIED TO HORN AND STROBE FOR | | NOTIFICATION IF NO BUILDING FIRE ALARM | | SYSTEM EXISTS. | | ALL AIR HANDLING EQUIPMENT OVER 2000 CFM | | WILL REQUIRE FAN SHUT DOWN BY DUCT SMOKE | | DETECTOR AND 1997 SMC 406.2 REQUIRES ALL | | EQUIPMENT SERVING AREAS USED FOR EGRESS | | EVEN IF LESS THAN 2000 CFM HAVE FAN SHUT | | DOWN BY DUCT SMOKE DETECTOR. |
|