2001-01-08 00:00:00 | BUILDING PLAN REVIEW: |
| 1:HANDICAPPED ACCESSABLE ROOMS BUILD "B" |
| SHEET A4: FLORIDA ACCESSABLITY CODE |
| A:9.1.3 SLEEPING ACCOMMODATIONS FOR |
| PERSONS WITH HEARING IMPAIRMENTS SHALL |
| COMPLY WITH 9.3 VISUAL ALARMS, NOTIF- |
| ICATION DEVICES & TELEPHONES. |
| B:9.1.5 IN ADDITION TO THE REQUIRED |
| SLEEPING ROOMS REQUIRED 9.1.5 REQUIRES |
| AT LEAST ONE SLEEPING ROOM OR SUITE |
| THAT COMPLIES WITH THE REQIUREMENTS OF |
| 9.3 VISUAL ALARMS,NOTIFICATION DEVISES |
| & TELEPHONES. |
| C:4.13.5 DOORS/CLEAR WIDTH: DOORWAYS |
| SHALL HAVE A CLEAR OPENING OF 32" WITH |
| THE DOOR OPEN 90 DEGREES, MEASURED |
| BETWEEN THE FACE OF THE DOOR AND THE |
| OPPOSITE STOP. |
| D:4.13.6 DOORS MANEUVERING CLEARENCES AT |
| DOORS.MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE SHOWN IN FIG. |
| 25. THE FLOOR OR GROUND AREA WITHIN |
| THE REQUIRED CLEARENCES SHALL BE LEVEL |
| AND CLEAR. |
| E:9.2.2REQUIREMENTS FOR ACCESIBLE UNITS, |
| SLEEPING ROOMS AND SUITES.MINIMUM |
| REQUIREMENTS:AN ACCESIBLE UNIT SHALL |
| BE ON AN ACCESIBLEROUTE COMPLYING |
| WITH 4.3, SHOW ON THE FLOOR PLAN THE |
| ELEMENTS (BED, CABINETS,DRAWER SPACE |
| CLOSETS & TELEPHONES). |
| 2:BEVERAGE AREA : 5.2 COUNTERS & BARS; |
| WHERE FOOD OR DRINK IS SERVED AT |
| COUNTERS EXCEEDING 34" IN HEIGTH FOR |
| CONSUMPTION BY THE CUSTOMERS SEATED ON |
| STOOLS OR STANDING AT TTHE COUNTER, A |
| PORTION OF THE MAIN COUNTER WHIICH IS |
| 60" IN LENGTH MINIMUM SHALLBE PROVIDED |
| IN COMPLIANCE WITH 4.32OR SERVICE |
| SHALL BE AVAILABLE AT ACCESSIBLE TABLE |
| WITH IN THE SAME AREA. |
| 3:LOBBY TELEPHONE TO COMPLY WITH FL. ACC |
| CODE 4.31 TELEEPHONES. |
| 4:LOBBY DOORS CLOUDED AREA: SHALL COMPLY |
| WITH FL ACC CODE 4.13.5 CLEAR WIDTH OF |
| 32".PLAN CALLS FOR2'-8" DOOR (2). |
| NONCOMPLIANCE. |
| 5:LOBBY DOORS AND GLAZED OPENING. SBC |
| 2405.2 SAFETY GLASS REQUIRED. |
| 6:SBC 1006.2.4 EXTERIOR STAIRS SHALL BE |
| SEPERATED FROM THE INTERIOR OF THE |
| BUILDING BY WALLS WITH A FIRE RESIS- |
| TANCE RATING OF NOT LESS THAN 1 HR. |
| WITH FIXED OR SELF CLOSING OPENING PRO |
| TECTIVES AS REQUIRED FOR ENCLOSED |
| STAIRS. THIS PROTECTION SHALL EXTEND |
| VERTICALLY FROM THE GROUND TO A POINT |
| 10 FT ABOVE THE TOPMOST LANDING OR THE |
| ROOF LINE, WHICHEVER IS LOWER, AND |
| HORIZONTALLY 10 FT FROM EACH SIDE OF |
| THE STAIRWAY. OPENINGS WITHIN THE 10 |
| FT HORIZONTAL EXTENSION OF THE PRO- |
| TECTED WALLS BEYOND THE STAIRWAY SHALL |
| BE EQUIPPED WITH FIXED 3/4-HOUR |
| ASSEMBLIES. THE GAS HEATER /METER MUST |
| NOT BE LOCATED BENEATH THE STAIRWELL. |
| 7:STANDARD BUILD CODE:1606.4/1707.4.1 |
| W.P.B. AMENDMENTS-EXTERIOR WINDOWS AND |
| DODR ASEMBLIES REPLACED WILL REQUIRE |
| PRODUCT APPROVAL REPORTS(2) FOR IMPACT |
| FROM WIND BORN DEBRIS, LARGE MISSLE |
| IMPACT TESTING. GLAZED OPENINGS THAT |
| DO NOT MEET THIS TESTING WILL NEED |
| TESTED SHUTTERS THAT DO HAVE APPROVED |
| TESTING AND ACCOMPINING REPORTS. WE |
| ACCEPT DADE COUNTY PRODUCT APP. OR |
| S.B.C.C.I. REPORT. |
| WE WILL ALSO NEED INFORMATION ON THE |
| 1-HR RAED WINDOW, AND ON THE 2ND FL |
| DOOR AS WELL AS THE 1ST FLOOR DOOR |
| DIRECTLY BELOW THE 2ND FLOOR LANDING. |
| 8:104.2.2: ON THE 2ND FLOOR PLAN THERE |
| IS A BEDROOM THAT HAS NO MEANS OF |
| EGRESS NOR DOES IT SHOW THE WINDOW, |
| THIS MAY ALSO REQUIRE A 1-HR FIRE |
| RATING IF LOCATED ON THE WALL OF THE |
| EXTERIOR STAIRS. |
| 9:104.2.2: THE PLANS DO NOT SHOW WHERE |
| THE HANDICAPPED PARKING AND PASSENGER |
| LOADING ZONES WILL BE? |
| |
| BUILDING PLAN REVIEW: |
| JIM WITMER |
| (561) 659-8096 EX 8412 |
| NOTES: |
| IF YOU HAVE ANY QUESTIONS,PLEASE CALL. |
| PLEASE RETURN THE REVIEWED PAGES WITH |
| THE CORRECTIONS IN ORDER TO EXPEDITE THE |
| REVIEW PROCESS.THANK YOU! |