Plan Review Notes
Plan Review Notes For Permit 00081232
Permit Number 00081232
Review Stop B
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00BUILDING PLAN REVIEW:
 1:HANDICAPPED ACCESSABLE ROOMS BUILD "B"
 SHEET A4: FLORIDA ACCESSABLITY CODE
 A:9.1.3 SLEEPING ACCOMMODATIONS FOR
 PERSONS WITH HEARING IMPAIRMENTS SHALL
 COMPLY WITH 9.3 VISUAL ALARMS, NOTIF-
 ICATION DEVICES & TELEPHONES.
 B:9.1.5 IN ADDITION TO THE REQUIRED
 SLEEPING ROOMS REQUIRED 9.1.5 REQUIRES
 AT LEAST ONE SLEEPING ROOM OR SUITE
 THAT COMPLIES WITH THE REQIUREMENTS OF
 9.3 VISUAL ALARMS,NOTIFICATION DEVISES
 & TELEPHONES.
 C:4.13.5 DOORS/CLEAR WIDTH: DOORWAYS
 SHALL HAVE A CLEAR OPENING OF 32" WITH
 THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE
 OPPOSITE STOP.
 D:4.13.6 DOORS MANEUVERING CLEARENCES AT
 DOORS.MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE SHOWN IN FIG.
 25. THE FLOOR OR GROUND AREA WITHIN
 THE REQUIRED CLEARENCES SHALL BE LEVEL
 AND CLEAR.
 E:9.2.2REQUIREMENTS FOR ACCESIBLE UNITS,
 SLEEPING ROOMS AND SUITES.MINIMUM
 REQUIREMENTS:AN ACCESIBLE UNIT SHALL
 BE ON AN ACCESIBLEROUTE COMPLYING
 WITH 4.3, SHOW ON THE FLOOR PLAN THE
 ELEMENTS (BED, CABINETS,DRAWER SPACE
 CLOSETS & TELEPHONES).
 2:BEVERAGE AREA : 5.2 COUNTERS & BARS;
 WHERE FOOD OR DRINK IS SERVED AT
 COUNTERS EXCEEDING 34" IN HEIGTH FOR
 CONSUMPTION BY THE CUSTOMERS SEATED ON
 STOOLS OR STANDING AT TTHE COUNTER, A
 PORTION OF THE MAIN COUNTER WHIICH IS
 60" IN LENGTH MINIMUM SHALLBE PROVIDED
 IN COMPLIANCE WITH 4.32OR SERVICE
 SHALL BE AVAILABLE AT ACCESSIBLE TABLE
 WITH IN THE SAME AREA.
 3:LOBBY TELEPHONE TO COMPLY WITH FL. ACC
 CODE 4.31 TELEEPHONES.
 4:LOBBY DOORS CLOUDED AREA: SHALL COMPLY
 WITH FL ACC CODE 4.13.5 CLEAR WIDTH OF
 32".PLAN CALLS FOR2'-8" DOOR (2).
 NONCOMPLIANCE.
 5:LOBBY DOORS AND GLAZED OPENING. SBC
 2405.2 SAFETY GLASS REQUIRED.
 6:SBC 1006.2.4 EXTERIOR STAIRS SHALL BE
 SEPERATED FROM THE INTERIOR OF THE
 BUILDING BY WALLS WITH A FIRE RESIS-
 TANCE RATING OF NOT LESS THAN 1 HR.
 WITH FIXED OR SELF CLOSING OPENING PRO
 TECTIVES AS REQUIRED FOR ENCLOSED
 STAIRS. THIS PROTECTION SHALL EXTEND
 VERTICALLY FROM THE GROUND TO A POINT
 10 FT ABOVE THE TOPMOST LANDING OR THE
 ROOF LINE, WHICHEVER IS LOWER, AND
 HORIZONTALLY 10 FT FROM EACH SIDE OF
 THE STAIRWAY. OPENINGS WITHIN THE 10
 FT HORIZONTAL EXTENSION OF THE PRO-
 TECTED WALLS BEYOND THE STAIRWAY SHALL
 BE EQUIPPED WITH FIXED 3/4-HOUR
 ASSEMBLIES. THE GAS HEATER /METER MUST
 NOT BE LOCATED BENEATH THE STAIRWELL.
 7:STANDARD BUILD CODE:1606.4/1707.4.1
 W.P.B. AMENDMENTS-EXTERIOR WINDOWS AND
 DODR ASEMBLIES REPLACED WILL REQUIRE
 PRODUCT APPROVAL REPORTS(2) FOR IMPACT
 FROM WIND BORN DEBRIS, LARGE MISSLE
 IMPACT TESTING. GLAZED OPENINGS THAT
 DO NOT MEET THIS TESTING WILL NEED
 TESTED SHUTTERS THAT DO HAVE APPROVED
 TESTING AND ACCOMPINING REPORTS. WE
 ACCEPT DADE COUNTY PRODUCT APP. OR
 S.B.C.C.I. REPORT.
 WE WILL ALSO NEED INFORMATION ON THE
 1-HR RAED WINDOW, AND ON THE 2ND FL
 DOOR AS WELL AS THE 1ST FLOOR DOOR
 DIRECTLY BELOW THE 2ND FLOOR LANDING.
 8:104.2.2: ON THE 2ND FLOOR PLAN THERE
 IS A BEDROOM THAT HAS NO MEANS OF
 EGRESS NOR DOES IT SHOW THE WINDOW,
 THIS MAY ALSO REQUIRE A 1-HR FIRE
 RATING IF LOCATED ON THE WALL OF THE
 EXTERIOR STAIRS.
 9:104.2.2: THE PLANS DO NOT SHOW WHERE
 THE HANDICAPPED PARKING AND PASSENGER
 LOADING ZONES WILL BE?
  
 BUILDING PLAN REVIEW:
 JIM WITMER
 (561) 659-8096 EX 8412
 NOTES:
 IF YOU HAVE ANY QUESTIONS,PLEASE CALL.
 PLEASE RETURN THE REVIEWED PAGES WITH
 THE CORRECTIONS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.THANK YOU!