Plan Review Notes
Plan Review Notes For Permit 00081232
Permit Number 00081232
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00MIN.SIZE OF H.C.SHOWERS SHALL COMPLY W/
 FACBC SEC.9.1.2,FIG.#57.
  
 2)PIPES UNDER H.C.LAV.SHALL BE INSULATE
 -ED PER FACBC SEC.4.19.4.
  
 3)SUBMIT DETAILS/MOUNTING HEIGHTS FOR
 ALL HANDICAP FIXTURES/APPURTENANCES.
 INCLUDE BENCH. OCT.1997 EDITION.
  
 4)INDICATE IF ANY RENOVATIONS WILL BE
 DONE ON THE EAST BUILDING AND IF SO,
 SUBMIT PLANS.
  
 5)THE INDIRECT WASTE IN THE BAR AREA
 SHALL DISCHARGE ABOVE THE FLOOR SINK
 PER SPC SEC.804.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.