Plan Review Notes
Plan Review Notes For Permit 00081147
Permit Number 00081147
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE:PLEASE SUBMIT PLANS SHOWING ALL
 BRANCH CIRCUIT #`S AND CORRELATE WITH
 PANEL SCHEDULES.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS!
 215-5
 ALSO PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% .
  
 3)NOTE: AIC RATINGS GIVEN FOR PANELS
 BUT ALSO NEED TO SUBMIT FOR MAIN DISC.
 PER 110-9 AND 215-5.
  
 4)NOTE:PLEASE SHOW GROUNDING ELECTRODE
 FOR TRANSFORMER.
  
 5)NOTE: PLANS SHOW MORE THAN WHAT PANEL
 SCHEDULES SHOW. PLEASE CLARIFY.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372
  
  
 ***6)NOTE: PLEASE SEE LOCAL CODE FOR
 COLOR CODING OF CONDUCTORS. 277/480V
 YOUR NOTES SHOW ORANGE AS "B" PHASE.