Notes |
Date |
Text |
2001-01-18 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | COMPLY WITH CITY CODE REQUIREMENTS. | | 2) NO INTERIOR FINISH INFORMATION | | PROVIDED WITH PLANS. | | 3) STORAGE ROOM TO BE AT LEAST ONE HOUR | | FIRE RATED AND BE EQUIPPED WITH A 45 | | MINUTE FIRE DOOR. A DOOR CLOSER IS | | REQUIRED. | | 4) PROVISIONS ARE TO BE MADE FOR AT | | LEAST TWO HANDICAPPED PERSONS. | | 5) INTERIOR DOOR TO MEETING ROOM TO | | SWING TOWARDS STORAGE ROOM WALL. | | 6) AWNINGS ARE TO BE FIRE RETARDANT. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|