Plan Review Notes For Permit 00080968 |
Permit Number |
00080968 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) MANUAL PULL STATION IN CUT SHEETS | | MAY NOT MEET CITY PLACE STANDARDS FOR | | DEVICE TYPE AND STYLE. | | 2) NO FLOOR PLAN WITH FIRE ALARM DEVICES | | SHOWN IN SUBMITTAL PACKAGE. | | 3) WHEN ACTIVATED THE FIRE ALARM SYSTEM | | IS TO BE AUDIBLE THROUGHOUT. | | 4) FIRE ALARM SYSTEM TO BE MONITORED BY | | A LICENSED UL LISTED FIRE ALARM COMPANY | | APPROVED BY THE FIRE RESCUE DEPARTMENT. | | 5) FIRE ALARM SYSTEM FOR CHEESECAKE | | FACTORY IS TO BE CONNECTED TO THE BASE | | BUILDING FIRE ALARM SYSTEM IN A RETAIL. | | 6) PLEASE PROVIDE FLOOR PLAN WITH | | FIRE ALARM DEVICES SHOWN FOR REVIEW | | PURPOSES. |
|