Plan Review Notes For Permit 00080950 |
Permit Number |
00080950 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************* PROVISO ****************** | | | | 1)NOTE: PLEASE PROVIDE PLANS WITH ALL | | BRANCH CIRCUIT #`S ON LAYOUT AND | | PLEASE CORRELATE WITH PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SUBMIT LOAD CALCULATION | | FOR PANEL SHOWING ALL CONTINUOUS LOADS | | AT 125%. YOU ARE ONLY TWO CIRCUITS ON | | PANEL SCHEDULE? | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | INSPECTION IS CALLED IN. IF THERE ARE | | ANY QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 659-8096 EXT 8372 |
|