Plan Review Notes For Permit 00080850 |
Permit Number |
00080850 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) ON AUGUST 16, 2000, WRITER SPOKE | | TO JOE CIPOLETTO OF ALARM GUARD BY | | TELEPHONE. WRITER ASKED WHAT TYPE OF | | WIRE IS TO BE USED HE RESPONDED 18 | | GAUGE, 4 CONDUCTOR, FPL 2204PP-2, RED | | FIRE WIRE. | | 2) SMOKE DETECTORS ARE TO BE INSTALLED | | A MINIMUM OF THREE FEET FROM AIR | | CONDITIONER DIFFUSERS. | | 3) MANUAL PULL STATIONS SHALL BE | | MOUNTED NO LOWER THAN 3 1/2 FEET AND NO | | MORE THAN 4 1/2 FEET FROM THE FLOOR. | | 4) HORN STROBE DEVICES TO BE MOUNTED | | BETWEEN 80-96 INCHES ABOVE THE FLOOR ON | | WALLS. | | 5) SYSTEM SUBJECT TO COMPLETE | | INSPECTION AFTER INSTALLATION BY FIRE | | RESCUE. |
|