2001-01-08 00:00:00SUBMIT COPY OF APPLICABLE GAS SIZING
 TABLE FOR THE P.E.& GALV.PIPE.SGC 305.4.
  
 PLANS SHOW 3/4"PIPE FROM METER SUPPLYING
 SYSTEM.COMPLY W/SGC TABLE 305.4(A)FOR
 APPLICABLE SIZE.(1 1/4" IS INADEQUATE).
  
 PLANS NOTE INTERIOR PIPING AS 102'.
 LENGTHS ON RISER DON'T CORRELATE.CLARIFY
  
 NOTE:A COPY OF THE APPLICABLE SIZING
 TABLE FOR EACH TYPE OF PIPE SHALL BE
 SUBMITTED W/PLANS.SEE ATTACHED.
  