Plan Review Notes
Plan Review Notes For Permit 00080678
Permit Number 00080678
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE COMPLETE INFORMATION FOR STORM
 PANELS UNDER A SEPARATE PERMIT.
 NOTE: INSTALLATION SCHEDULE IS NOT
 CORRECT. SAME COMMENT WAS ADDRESSED
 SEVERAL TIMES BEFORE, BUT IT WAS NEVER
 CORRECTED.
 PLEASE, PROVIDE A CORRECT INSTALLATION
 SCHEDULE. SEE APPROVED STORM PANEL
 DRAWINGS. SELECT ANCHOR TYPE AND THE
 REQUIRED SPACING ACCORDING TO THE MEAN
 ROOF HEIGHT, DESIGN PRESSURES, EDGE
 DISTANCE, CONNECTION TYPE & STRUCTURE
 TYPE TO BE ATTACHED TO.
 NOTE: KEEP IN MIND THIS IS MASONRY
 CONSTRUCTION, NOT 3000PSI CONCRETE.
 2-FLOOD ZONE "AO". WILL NEED TO PROVIDE
 ELEVATION CERTIFICATE.
 3-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT FRONT AND
 BACK PORCH. INCLUDING FASTENER TYPES
 AND SPACING. SECTION 2504.2 SBC 1997.
 4-PROVIDE PRODUCT APPROVAL FOR ONE HOUR
 FIRE RATE GLASS BLOCK.
 5-PRODUCT APPROVAL FOR ENTRY DOOR IS
 MISSING THE APPROVED DRAWINGS. ALSO,
 MAKE SURE THEY ARE LEGIBLE.