Plan Review Notes For Permit 00080678 |
Permit Number |
00080678 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-PROVIDE COMPLETE INFORMATION FOR STORM | | PANELS UNDER A SEPARATE PERMIT. | | NOTE: INSTALLATION SCHEDULE IS NOT | | CORRECT. SAME COMMENT WAS ADDRESSED | | SEVERAL TIMES BEFORE, BUT IT WAS NEVER | | CORRECTED. | | PLEASE, PROVIDE A CORRECT INSTALLATION | | SCHEDULE. SEE APPROVED STORM PANEL | | DRAWINGS. SELECT ANCHOR TYPE AND THE | | REQUIRED SPACING ACCORDING TO THE MEAN | | ROOF HEIGHT, DESIGN PRESSURES, EDGE | | DISTANCE, CONNECTION TYPE & STRUCTURE | | TYPE TO BE ATTACHED TO. | | NOTE: KEEP IN MIND THIS IS MASONRY | | CONSTRUCTION, NOT 3000PSI CONCRETE. | | 2-FLOOD ZONE "AO". WILL NEED TO PROVIDE | | ELEVATION CERTIFICATE. | | 3-PROVIDE COMPLETE SPECIFICATIONS FOR | | CEILING CONSTRUCTION AT FRONT AND | | BACK PORCH. INCLUDING FASTENER TYPES | | AND SPACING. SECTION 2504.2 SBC 1997. | | 4-PROVIDE PRODUCT APPROVAL FOR ONE HOUR | | FIRE RATE GLASS BLOCK. | | 5-PRODUCT APPROVAL FOR ENTRY DOOR IS | | MISSING THE APPROVED DRAWINGS. ALSO, | | MAKE SURE THEY ARE LEGIBLE. |
|