Plan Review Notes For Permit 00080487 |
Permit Number |
00080487 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)NOTE SQ.FEET OF SPACE ON PLANS TO | | ENSURE COMPLIANCE W/SPC TABLE 407 FOR | | PLBG.FIXTURES. | | | | 2)A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407.BOTTLED WATER IS NOT ACCEPT- | | ABLE IN LIEU OF FOUNTAIN. | | | | 3)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | SEC.4.1.3(10)(A).4.15.PROVISIONS SHALL | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | BENDING OR STOOPING. | | | | 4)A FLOOR DRAIN IS REQD.IN THE TOILET | | ROOM PER SPC SEC.409.4.1.1. | | | | 5)MOUNTING HEIGHTS OF HANDICAP FIXTURES | | SHALL COMPLY W/FACBC OCT.1997 EDITION. |
|