Plan Review Notes For Permit 00080409 |
Permit Number |
00080409 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED; | | | | 1.NEED MANUFACTORS SPECIFICATIONS FOR | | GAS LIGHTS. | | | | 2.SHOW LONGEST RUN IN FEET. | | | | 3.LINE ONE HAS 16 LIGHTS NOT 14. | | | | 4.USE TABLE 305.4E TO SIZE PE PIPE. | | | | 5.FUTURE LOAD MUST BE LISTED FOR LINE | | TWO SO PIPE SIZING WILL BE CORRECT | | WHEN FUTURE APPL. ARE ADDED. | | | | 6.SIZE PIPE AT METER. | | | | 7.GALVANIZED PIPE TO BE USED ABOVE | | GROUND. | | | | 8.IF GAS PIPE RUNS IN CONCRETE COLUMN | | GAS PIPE MUST BE SLEAVED. | | | | GAS PLAN REVIEW BY; | | JOHN LEECH | | 659-8096 EXT. 8377 |
|