Plan Review Notes
Plan Review Notes For Permit 00080409
Permit Number 00080409
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00DENIED;
  
 1.NEED MANUFACTORS SPECIFICATIONS FOR
 GAS LIGHTS.
  
 2.SHOW LONGEST RUN IN FEET.
  
 3.LINE ONE HAS 16 LIGHTS NOT 14.
  
 4.USE TABLE 305.4E TO SIZE PE PIPE.
  
 5.FUTURE LOAD MUST BE LISTED FOR LINE
 TWO SO PIPE SIZING WILL BE CORRECT
 WHEN FUTURE APPL. ARE ADDED.
  
 6.SIZE PIPE AT METER.
  
 7.GALVANIZED PIPE TO BE USED ABOVE
 GROUND.
  
 8.IF GAS PIPE RUNS IN CONCRETE COLUMN
 GAS PIPE MUST BE SLEAVED.
  
 GAS PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377