2001-01-08 00:00:00 | **************** PROVISO *************** | | | | 1)NOTE: SINCE FIRST REVIEW YOU ARE NOW | | SHOWING A COMPLETE NEW SERVICE RISER. | | PLEASE SUBMIT AIC RATINGS OF EQUIPMENT | | MAINS AND PANELS BEING INSTALLED. | | PER 110-9 AND 215-5 | | | | 2)NOTE: PLEASE SUBMIT COMPLETE REVISED | | PANEL SCHEDULES.215-5 | | | | 3)NOTE: PLEASE CLARIFY WIRE FEEDING | | 125A PANEL. SHOWS 3# L.?? | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW BEFORE FINAL ELECTRICAL | | INSPECTION IS CALLED IN. | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 659-8096 EXT 8372 |
|