2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 OF EXISTING AND NEW. 220-3-C-1
  
 2)NOTE: PLEASE LIST THE BATH(S) CIRCUITS
 PER 210-11-C-3 ON PANLE SCHEDULE.
  
 3)NOTE: PLEASE MAKE NOTE AS TO ANY NEW
 BLDG. STEEL TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM 250-50
  
 4)NOTE: PANEL'A' SHOWS AS BEING 125AMP?
 RISER DIAGRAM SHOWS AS 200AMP.??
 PLEASE CORRELATE TO WHICH ONE IS CORRECT
 SHOW SIZE OF EXISTING SERVICE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESITONS
 PLEASE CALL.
  