2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | OF EXISTING AND NEW. 220-3-C-1 | | | | 2)NOTE: PLEASE LIST THE BATH(S) CIRCUITS | | PER 210-11-C-3 ON PANLE SCHEDULE. | | | | 3)NOTE: PLEASE MAKE NOTE AS TO ANY NEW | | BLDG. STEEL TO BE PART OF THE GROUNDING | | ELECTRODE SYSTEM 250-50 | | | | 4)NOTE: PANEL'A' SHOWS AS BEING 125AMP? | | RISER DIAGRAM SHOWS AS 200AMP.?? | | PLEASE CORRELATE TO WHICH ONE IS CORRECT | | SHOW SIZE OF EXISTING SERVICE. | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESITONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 659-8096 EXT 8372 |
|