Plan Review Notes For Permit 00080048 |
Permit Number |
00080048 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM WHEN ACTIVATED IS | | TO BE AUDIBLE THROUGHOUT BUILDING. | | 2) CONTROL DEVICES ON BACKFLOW AND POST | | INDICATOR VALVE ARE TO BE SUPERVISED. | | 3) DISTANCES BETWEEN MANUAL PULL | | STATIONS ARE NOT TO EXCEED 200 FEET. | | 4) SYSTEM TO BE MONITORED BY A UL | | LISTED CENTRAL STATION APPROVED BY | | THE FIRE RESCUE DEPARTMENT. |
|