2001-01-08 00:00:00ARCHITECT'S ROOF FRAMING PLAN REVISION:
 1-ARCHITECT TO REVIEW ALL TRUSS DRAWINGS
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 2-CONNECTORS SPECIFIED FOR TRUSSES
 HG-12, MG-24, MH-7F, MHG-X AND TGD-1
 DON'T WORK. SEE ENGINEERED TRUSSES
 PROFILE.
  
 3-TRUSS FRAMING LAYOUT BY FAMILY ROOM
 AREA IS DIFFERENT FROM THE ARCHITECT'S
 SPECIFY CONNECTORS AS REQUIRED. SEE
 TRUSSES PROFILE AND LOADS.
  
 4-SEE SHEET A-5 FOR COMMENTS.
  
  
  
  
 NOTE:
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CALL JULIO GOMEZ AT 659-8096
 EXT. 8232.