2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-PROVIDE PRODUCT APPROVAL FOR: |
| -BUTT GLAZING SYSTEM AT FAMILY AREA. |
| -CUSTOM MADE KITCHEN WINDOW ASSEMBLY. |
| -ENTRY DOORS W/ TRANSOM ABOVE ASSEMBLY. |
| -FRENCH DOOR W/ TRANSOM ABOVE ASSEMBLY. |
| (SEE COMMENTS ON SUBMITTAL). |
| -SLIDING GLASS DOORS WITH TRANSOM ABOVE |
| ASSEMBLY (SEE COMMENTS ON SUBMITTAL). |
| -GARAGE DOORS PRODUCT APPROVALS THAT |
| MEET THE DESIGN PRESSURES CALCULATED |
| BY THE ARCHITECT. |
| 2-COMPLETELY SPECIFY CEILING CONSTRUCT'N |
| AT ENTRY AND REAR PORCHES. |
| NOTE: INCLUDE FASTENER TYPES AND |
| SPACING. SECTION 2504 SBC 1997. |
| 3-STORM PANELS TO BE UNDER A SEPARATE |
| PERMIT. (NO INFO. GIVEN AT THIS TIME). |
| 4-TRUSS DRAWINGS: |
| -PROVIDE 2 COMPLETE SETS OF ENGINEERED |
| TRUSS DRAWINGS,SIGNED, SEALED AND DATE |
| -ENGINEER TO SIGN, SEAL AND DATE TRUSS |
| DRAWINGS AS WELL. |
| NOTE: DON'T FORGET TO PROVIDE ALL THE |
| INFORMATION REQUIRED BY FLORIDA |
| STATUTE 471 WHEN SUBMITTING DOCUMENTS |
| FOR PUBLIC RECORDS (NAME, LICENSE #, |
| ADDRESS, ETC.). |
| -ARCHITECT TO REVIEW ALL TRUSS DRAWINGS |
| PRIOR TO SUBMITTAL TO THIS OFFICE. |
| 5-PROVIDE SAFETY GLASS AS REQUIRED AT |
| MASTER BATH, BEDROOM #3, LIVING ROOM, |
| GARAGE (IF EDGE OF WINDOW IS LESS THAN |
| 18" ABOVE FINISH FLOOR). SEE PLANS. |
| SECTION 2405.2 SBC 1997. |
| 6-SEE COMMENTS ON PLANS & REVISE/UPDATE |
| DRAWINGS AS REQUIRED. |
| |
| |
| |
| |
| |
| NOTE: |
| -PLEASE SUBMIT INFORMATION REQUIRED ON |
| THIS PROVISO PRIOR TO CONSTRUCTION OR |
| INSTALLATION IN ORDER TO AVOID DELAYS. |