Plan Review Notes For Permit 00071328 |
Permit Number |
00071328 |
|
Review Stop |
FS |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) FIRE DEPARTMENT CONNECTION IS TO BE | | INSTALLED NO FARTHER THAN 150 FEET FROM | | A FIRE HYDRANT. | | 2) ACCORDING TO THE PLANS, THE RISER | | AND FIRE DEPARTMENT CONNECTION ARE | | PLANNED NEAR THE NORTHWEST CORNER OF | | THE BUILDING. IT WAS DISCUSSED WITH | | MIKE MOORE OF FARMER AND IRWIN ON | | JUNE 28, 2000, THAT IT IS NOT KNOWN | | WHAT OTHER BUILDINGS ARE PLANNED TO | | THE WEST OF THE GOURMET MARKET. THE | | DEPARTMENT CONNECTION SHOULD BE | | RELOCATED. | | 3) ENTIRE BUILDING IS TO BE PROTECTED | | BY FIRE SPRINKLER HEADS TO INCLUDE | | FREEZERS, COOLERS, ELECTRICAL, | | MECHANICAL AND SERVICE ROOMS. | | 4) INSTALLATION SUBJECT TO FIRE RESCUE | | APPROVAL. |
|