2001-01-08 00:00:00 | *************DENIED******************** | | 1. PROVIDE OUTSIDE AIR CALCULATIONS PER | | ASHRAE 62-89 | | 2. DUCT SMOKE DETECTOR TO BE TIED TO | | BLDG FIRE ALARM PER 1996 NFPA 90A 4-4.4. | | 3. SENSIBLE CAPACITY OF SELECTED AHU | | SHALL NOT EXCEED 20% OF THE CALCULATED | | SENSIBLE LOAD.(PGAL) | | 4. SUBMIT ENERGY CALCULATION FORM 400B. | | (PGAL) | | 5. INDICATE LOCATION OF REQUIRED FIRE | | DAMPERS PER 1997 SMC 610 (PLAN INDICATES | | RATED CEILING SEE SHEET A-8) |
|