Plan Review Notes For Permit 00071187 |
Permit Number |
00071187 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE: PLEASE SUBMIT CLARIFICATION ON | | FEEDER SIZES. ONE SHOWS 3/0 AND THE | | OTHER 1/0. PANEL "A" | | | | 2)NOTE;PLEASE HAVE PANEL REFLECT MCB AS | | REQ` BY NEC. | | | | 3)NOTE: PLEASE INCLUDE SHOW WINDOW OUT- | | -LETS AS PER 210-62 AND FIGURE THE LOAD | | INTO LOAD CALCS FROM 220-12B. | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | AT 125% (LIGHTING) | | | | 4)NOTE: A DISCONNECT IS SHOWNBUT NO | | INFORMATION IS GIVEN? PLEASE PROVIDE | | INFORMATION ON THIS DISCONNECT ON | | RISER DIAGRAM. | | | | 5)NOTE:PLEASE PROVIDE AIC RATING FOR | | THE DISCONNECT.110-9 | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATIONB | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | CITY OF WEST PALM BEACH | | 659-8096 EXT 8372 | | ELECTRICAL PLAN REVIEW. |
|