2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION ON
 FEEDER SIZES. ONE SHOWS 3/0 AND THE
 OTHER 1/0. PANEL "A"
  
 2)NOTE;PLEASE HAVE PANEL REFLECT MCB AS
 REQ` BY NEC.
  
 3)NOTE: PLEASE INCLUDE SHOW WINDOW OUT-
 -LETS AS PER 210-62 AND FIGURE THE LOAD
 INTO LOAD CALCS FROM 220-12B.
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% (LIGHTING)
  
 4)NOTE: A DISCONNECT IS SHOWNBUT NO
 INFORMATION IS GIVEN? PLEASE PROVIDE
 INFORMATION ON THIS DISCONNECT ON
 RISER DIAGRAM.
  
 5)NOTE:PLEASE PROVIDE AIC RATING FOR
 THE DISCONNECT.110-9
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATIONB
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372
 ELECTRICAL PLAN REVIEW.