Plan Review Notes
Plan Review Notes For Permit 00071044
Permit Number 00071044
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)CLEARLY SHOW WIDTH OF TOILET ROOMS ON
 THE PLAN.THE DIMENSIONS ON SHT.A-10 ARE
 ILLEGIBLE.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 2)SHT.A-3-DOOR CANNOT SWING INTO CLEAR
 FLOOR SPACE FOR DRINKING FOUNTAIN.FACBC
 SEC.4.22.2.
  
 3)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 4)SUBMIT OCCUPANT LOAD PER SPC TABLE 407
 SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT-
 IBLE AREAS.(STOCKROOM CANNOT BE DELETED)
  
 5)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
  
 6)SHOW DIMENSIONS/MOUNTING HEIGHTS OF
 ALLHANDICAP FIXTURES AND APPURTENANCES
 THE DIMENSIONS ON SHT.A-10 ARE ILLEGIBLE
  
 7)WALLS AND FLOORS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO 4' PER SBC SEC.1204.2
  
 8)SEE ATTACHED REQS.FOR TOILET ROOMS
 LOCATED IN STORAGE ROOMS
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.