Plan Review Notes For Permit 00071044 |
Permit Number |
00071044 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)CLEARLY SHOW WIDTH OF TOILET ROOMS ON | | THE PLAN.THE DIMENSIONS ON SHT.A-10 ARE | | ILLEGIBLE.COUNTYWIDE AMENDMENTS TO SPC | | SEC.104.2.1. | | | | 2)SHT.A-3-DOOR CANNOT SWING INTO CLEAR | | FLOOR SPACE FOR DRINKING FOUNTAIN.FACBC | | SEC.4.22.2. | | | | 3)DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | OR STOOPING. | | | | 4)SUBMIT OCCUPANT LOAD PER SPC TABLE 407 | | SEE SPC SEC.407.1.3.FOR ALLOWED DEDUCT- | | IBLE AREAS.(STOCKROOM CANNOT BE DELETED) | | | | 5)AN ADDITIONAL LAVATORY IS REQD.IN THE | | WOMEN'S TOILET ROOM PER SPC TABLE 407. | | | | 6)SHOW DIMENSIONS/MOUNTING HEIGHTS OF | | ALLHANDICAP FIXTURES AND APPURTENANCES | | THE DIMENSIONS ON SHT.A-10 ARE ILLEGIBLE | | | | 7)WALLS AND FLOORS IN TOILET ROOMS SHALL | | BE NONABSORBENT TO 4' PER SBC SEC.1204.2 | | | | 8)SEE ATTACHED REQS.FOR TOILET ROOMS | | LOCATED IN STORAGE ROOMS | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|