Plan Review Notes
Plan Review Notes For Permit 00071044
Permit Number 00071044
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER SYSTEM DRAWINGS.
 2) EXITING THROUGH STOCKROOM PERMITTED
 ONLY IF: NOT MORE THAN 50 PERCENT OF
 EXIT ACCESS IS PROVIDED THROUGH
 STOCKROOM, STOCKROOM NOT SUBJECT TO
 LOCKING, MAIN AISLE THROUGH STOCKROOM
 SHALL BE AT LEAST 44 INCHES AND BE
 MAINTAINED AT THAT WIDTH.
 3) RED AWNING IS TO BE FIRE RETARDANT
 SHOWN ON SHEET A-6.
 4) INTERIOR FINISH TO BE CLASS A OR B.
 5) PORTABLE FIRE EXTINGUISHERS REQUIRED.