Plan Review Notes For Permit 00071044 |
Permit Number |
00071044 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | FOR FIRE SPRINKLER SYSTEM DRAWINGS. | | 2) EXITING THROUGH STOCKROOM PERMITTED | | ONLY IF: NOT MORE THAN 50 PERCENT OF | | EXIT ACCESS IS PROVIDED THROUGH | | STOCKROOM, STOCKROOM NOT SUBJECT TO | | LOCKING, MAIN AISLE THROUGH STOCKROOM | | SHALL BE AT LEAST 44 INCHES AND BE | | MAINTAINED AT THAT WIDTH. | | 3) RED AWNING IS TO BE FIRE RETARDANT | | SHOWN ON SHEET A-6. | | 4) INTERIOR FINISH TO BE CLASS A OR B. | | 5) PORTABLE FIRE EXTINGUISHERS REQUIRED. |
|