Plan Review Notes For Permit 00071044 |
Permit Number |
00071044 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | | | | | 1. FLORIDA ENERGY CALULATIONS MUST BE | | SIGNED BY THE OWNER/ AGENT | | 2. PROVIDE PRODUCT APPROVAL FOR IMPACT | | RESISTANT WINDOW GLAZING FOR STOREFRONT/ | | METRO DADE COUNTY OR SBCCI SSTD12-97 | | 3. SUBMIT FIRE SPRINKLER APPLICATION AND | | PLANS, FIRE SPRINKLER PERMIT MUST BE | | ISSUED PRIOR TO BUILDING PERMIT BEING | | ISSUED. | | 4. SHEET A-5 COVE DETAIL INDICATES WOOD | | CEILING JOIST,NOT PERMITED (BUILDING IS | | TYPE 2 CONSTRUCTION) | | ALL WOOD FRAMING TO BE FIRE RETARTANT | | TREATED. 1997 SBC CHAPTERS 6 & 7 |
|