Plan Review Notes
Plan Review Notes For Permit 00071044
Permit Number 00071044
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00 
  
 1. FLORIDA ENERGY CALULATIONS MUST BE
 SIGNED BY THE OWNER/ AGENT
 2. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOW GLAZING FOR STOREFRONT/
 METRO DADE COUNTY OR SBCCI SSTD12-97
 3. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS, FIRE SPRINKLER PERMIT MUST BE
 ISSUED PRIOR TO BUILDING PERMIT BEING
 ISSUED.
 4. SHEET A-5 COVE DETAIL INDICATES WOOD
 CEILING JOIST,NOT PERMITED (BUILDING IS
 TYPE 2 CONSTRUCTION)
 ALL WOOD FRAMING TO BE FIRE RETARTANT
 TREATED. 1997 SBC CHAPTERS 6 & 7