2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BLD STEEL ALSO.250-50
  
 2)NOTE: MISSING AIC RATING FOR MAINS/
 PANEL.110-9
  
 3)NOTE: PLEASE LIST BATH(S) CIRCUIT(S)
 AS PER 210-11-C-3 MUST BE 20 AMP AND #12
 AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW