2001-01-08 00:00:001)LAVATORIES IN RESTROOMS INFRINGE ON
 CLEAR FLOOR SPACE FOR WATER CLOSET.
 COMPLY W/FACBC SEC.4.17.3.FIGURE 30(A).
  
 2)PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 3)CLEANOUTS IN GREASY WASTE AND SANITARY
 SHALL COMPLY W/ SPC SEC.710.2.
  
 4)UNION REQD.DOWNSTREAM OF MANUAL
 CONTROL VALVE FOR SYSTEM PER NFPA 54,
 SEC.5.5.4.
  
 5)SANITARY SYSTEM FOR TOILET ROOMS SHALL
 COMPLY W/SPC SEC.914.1 FOR CIRCUIT AND
 LOOP SYSTEM.
  
 6)WATER HEATER RELIEF LINE SHALL NOT
 DISCHARGE TO THE GREASE SYSTEM PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.4
  
 7)INDICATE TYPE OF MATERIAL USED FOR THE
 GAS SYSTEM.RECALCULATE YOUR BTU LOAD ON
 THE SYSTEM.
  
 8)GAS SYSTEM IS NOT PROPERLY SIZED PER
 SGC SEC.305.4.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY COMMENTS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.