Plan Review Notes For Permit 00070815 |
Permit Number |
00070815 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | THIS REVIEW OCCURRED AFTER DEAN RUNNELS | | OF BUILDING AND ZONING MET WITH | | REPRESENTATIVES FOR MARKS ON THE PARK, | | AUGUST 10, 2000. | | 1) OCCUPANT LOAD TO BE DETERMINED BY | | THIS OFFICE. | | 2) DURING THE MEETING THEY ADVISED THAT | | CITY PLACE PARTNERS IS GOING TO | | PROVIDE INFORMATION SO THAT FIRE ALARM | | EQUIPMENT CAN BE INSTALLED WITHIN THE | | SPACE. | | 3) AN ADDITIONAL ILLUMINATED EXIT SIGN | | TO BE INSTALLED TO DIRECT PERSONS TO | | THE NEW FIRE RATED EXIT HALLWAY. | | 4) PORTABLE FIRE EXTINGUISHERS SHOWN ON | | RED-LINED DRAWING TO BE AT LEAST 5LBS | | WITH A MINIMUM OF 2A10BC FIRE RATING. | | 5) PROVIDE SEPARATE PLANS AND PERMIT FOR | | HOOD, DUCT AND EXTINGUISHING SYSTEM. | | 6) ACCORDING TO THE LETTER WRITTEN TO | | DEAN RUNNELS OF B&Z, FIRE SPRINKLER | | DRAWINGS ARE EXPECTED WITHIN THE WEEK. | | APPROVED PROVISO |
|