2001-01-08 00:00:00 | | | | | | | | | | | | | 1. PROVIDE LETTER FROM SPECIAL INSPECTOR | | 2. PROVIDE PRODUCT APPROVAL SHEETS ON | | EXTERIOR GLAZING AS PER METRO DADE | | COUNTY OR 1997 SSTD 12-97 | | 3. FIRE SPRINKLER PERMIT MUST BE ISSURED | | PRIOR TO ISSURANCE OF BUILDING PERMIT | | 4. 1997 SBC | | A)ALL LUMBER IN FRAMING MUST BE FIRE | | RETARDANT TREATED WOOD CHAPTERS 6&7 | | B)SHEET 1D-8 REMOVE STEP-UP TO SEATING | | OR MAKE HANDICAP ACCESSIBLE. | | C)NO SECOND EXIT, EXIT THROUGH KITCHEN | | NOT ALLOWED | | 5. 1997 FLORIDA HANDICAP CODE | | A)PROVIDE DETAILS SHOWING TURNING | | RADIUS IN RESTROOMS | | B)PROVIDE DETAIL SHOWING SLOPE ON ALL | | RAMPS | | 6. ADDRESS FOR BUILDING "B" IS 700 | | SOUTH ROSEMARY NOT 701S. ROSEMARY |
|